How it's calculated
Evaporation. E = 0.00085 × Q × R, with E and circulating flow Q in gpm and range R in °F. About 1% of circulation evaporates per 10 °F of range; the 0.85 factor allows for the share of heat that leaves as sensible rather than latent heat. Humid climates run lower and dry ones higher, so the coefficient is an input.
Makeup and blowdown. Cycles of concentration C is the ratio of makeup to blowdown. At steady state, makeup M = E × C / (C − 1) and blowdown plus drift = E / (C − 1).
Flow. Water-cooled chillers are rated with 85 °F entering condenser water at 3.0 gpm per ton (AHRI 550/590), which gives a range of about 10 °F. Use your measured flow if you have it.
Questions
How much water does a cooling tower evaporate?
Roughly 1% of the circulating flow for every 10 °F of range, or 0.00085 × flow (gpm) × range (°F) for average conditions. A 500-ton plant at 3 gpm per ton and a 10 °F range evaporates about 12.75 gpm at full load.
What is the makeup water formula for a cooling tower?
Makeup = evaporation × C / (C − 1), where C is the cycles of concentration. Blowdown plus drift = evaporation / (C − 1).
Why does blowdown matter?
Blowdown is what keeps dissolved minerals from concentrating to the point of scale. It is also water you pay for twice, once as makeup and again as sewer charges in many cities.